最新文章专题视频专题问答1问答10问答100问答1000问答2000关键字专题1关键字专题50关键字专题500关键字专题1500TAG最新视频文章推荐1 推荐3 推荐5 推荐7 推荐9 推荐11 推荐13 推荐15 推荐17 推荐19 推荐21 推荐23 推荐25 推荐27 推荐29 推荐31 推荐33 推荐35 推荐37视频文章20视频文章30视频文章40视频文章50视频文章60 视频文章70视频文章80视频文章90视频文章100视频文章120视频文章140 视频2关键字专题关键字专题tag2tag3文章专题文章专题2文章索引1文章索引2文章索引3文章索引4文章索引5123456789101112131415文章专题3
当前位置: 首页 - 正文

3300-3说明书

来源:动视网 责编:小OO 时间:2025-09-25 13:45:24
文档

3300-3说明书

SpecificationsandOrderingInformationPartNumber141524-01Rev.F(04/07)DescriptionTheSystemMonitorperformsfourimportanttasksina3300monitorrack,providing:Functionscommontoallmonitorsintherack,suchas:-Alarmsetpointadjustment-Keyphasor®power,termination,co
推荐度:
导读SpecificationsandOrderingInformationPartNumber141524-01Rev.F(04/07)DescriptionTheSystemMonitorperformsfourimportanttasksina3300monitorrack,providing:Functionscommontoallmonitorsintherack,suchas:-Alarmsetpointadjustment-Keyphasor®power,termination,co
Specifications and Ordering Information

Part Number 141524-01

Rev. F (04/07)

Description

The System Monitor performs four important tasks in a 3300 monitor rack, providing:

Functions common to all monitors in the rack, such as:

- Alarm setpoint adjustment

- Keyphasor ® power, termination, conditioning, and distribution - Alarm acknowledgement

Connection of all installed monitors to an external communications processor (sold separately) via STATIC and DYNAMIC data ports.

Optional Serial Data Interface (SDI) for communication of transducer and monitor data to process computers, digital/distributed control systems, programmable controllers, and other control and automation systems.

Optional Dynamic Data Interface (DDI) for communication of transducer and monitor data to compatible Bently Nevada machinery management software. Depending on the type of data required, this option may eliminate the need for an external communications processor.

Warning

A transducer field wiring failure, monitor failure, or loss of primary power can cause loss of machinery protection. This could result in property damage and/or bodily injury. Therefore, we strongly recommend connection of an external (operator control panel mounted) annunciator to the OK Relay terminals.

Inputs

Power

Consumption:

2 watts; 4.6 watts with interface

options.

Keyphasor

Signal:

Accepts up to four proximity

probe Keyphasor signals.

Input

impedance:

10 k Ω.

RS422

Communications

Impedance:

4 k Ω.

Threshold:

0.2 V.

Baud Rate:

19.2 k baud maximum for SDI;

38.4 k baud maximum for DDI. Distance:

1200 metres (4000 feet)

maximum.

RS232

Communications

Impedance:

3 k Ω to 7 k Ω.

Input Levels:

High +3 to +25 V;

Low -3 to -25V.

Baud Rate:

19.2 k baud maximum for

SDI and DDI.

Distance:

30 metres (100 feet) maximum. Keyphasor®

Signals Frequency

Range:

60 to 30,000 cpm (rpm).

Duty Cycle:

1% minimum.

Amplitude:

0.5 V peak-to-peak minimum.

dc Signal

Range:

0 to -24 V (VT = -24 Vdc);

0 to -18 V (VT = -18 Vdc).

Signal Conditioning

Frequency

Range:

Determined by software (user-

selectable); 10 kHz maximum. Accuracy -

Dynamic Signal:

± 0.3% of full-scale, typical, at

25°C (77°F);

±0.7% of full-scale, maximum, at

25°C (77°F).

Phase:

±0.2°, typical, at 25°C (77°F);

±1°, maximum, at 25°C (77°F). Gap:

0.3% of dc Signal Range, typical. RPM:

±1 rpm, typical.

Outputs

Buffered

Keyphasor

Outputs:

Four coaxial connectors on front

panel.

Output

Impedance:

100 Ω.

Specifications and Ordering InformationKeyphasor

Transducer

Power Supply:

User-programmable for -24 Vdc

or -18 Vdc. Voltages are short-

circuit protected.

Indicators:

Three LEDs on front panel Supplies OK:

ON when all system supply

voltages are within tolerance.

LEDs behind the slide-away front

panel indicate the condition of the

various monitored supply

voltages. The appropriate Supply

voltage LED and the SUPPLIES OK

LED on the front panel turn OFF if

a voltage is out of tolerance.

Trip Multiply:

ON when Trip Multiply function is

active.

Data Interface

OK:

OFF when either the SDI or the

DDI hardware is not functioning

properly or is not installed.

RS422

Communications

Levels:

High 2.5 V, minimum;

Low 0.5 V, maximum.

Baud Rate:

19.2 k baud, maximum, for SDI;

38.4 k baud, maximum, for DDI. Distance:

1200 metres (4000 feet),

maximum.

RS232

Communications

Levels:

High +5 V, minimum;

Low -5 V, maximum.

Baud Rate:

19.2 k baud, maximum,

for SDI and DDI.

Distance:

30 metres (100 feet), maximum. Controls

Front Panel:

Two switches control the Up and

Down adjustment of monitor

alarm setpoints. A third switch

controls the alarm RESET function. Rear Panel:

Terminals provide connections for

Rack Inhibit, Trip Multiply, and

Alarm Reset contact closures. Communications:

RS232 or RS422 communication

links. One connection to host

computer and one connection for

daisy chaining to the next rack. RS232 Interface:

150 baud to 19.2 k baud; 30

metres (100 feet) maximum.

RS422 Interface:

150 baud to 19.2 k baud for SDI;

150 baud to 38.4 k baud for DDI;

1200 metres (4,000 feet)

maximum.

Environmental Limits

Operating

Temperature:

0°C to +65°C (+32°F to +150°F). Storage

Temperature:

-40°C to +85°C (-40°F to +185°F). Relative

Humidity:

To 95%, noncondensing.

EMC Directive

Certificate of

Conformity:

158710

Specifications and Ordering InformationLow Voltage

Directive

Certificate of

Conformity:

135300

Hazardous Area Approvals

Approval Option

(01)

Class I, Div 2

Groups A, B, C, D

T4 @ Ta = -20 °C to +65 °C

(-4 °F to +150 °F)

Certification

Number

CSA 150368-1002151 (LR 26744) ATEX

Approval Option

(02)

For Selected Ordering Options

with ATEX/CSA agency

approvals:

II G

EEx nC[L] IIC

T4 @ Ta = -20°C to +60°C Certification

Number

BN26744C-55A

Physical

Rack Space

Requirements:

One rack position, installs only in

position two (next to the Power

Supply).

Weight:

0.9 kg (2.2 lbs.). Communications

Protocol:

Either Modicon Modbus® or

Allen-Bradley DF1 protocol (switch

selectable); RS422 or RS232

cabling (jumper-selectable). Data

available via this interface

includes the following on a per

channel basis:

Proportional value for each

monitored variable (available as

current values and a Fast Trend

file)

Proportional value for probe gap

voltage (for proximity probe

channels)

OK status

Alert and Danger alarm status

Bypass status (channel and

monitor)

Trip Multiply status (rack)

Monitor alarm setpoints (Modicon

Modbus only)

Address Setting:

Eight jumpers on the Serial Data

Interface allow setting of up to

256 different addresses.

Baud Rate:

Four jumpers are used to set the

desired baud rate for serial

communications; 19.2 k baud,

maximum.

Message

Checking:

One jumper selects between

Cyclic Redundancy Check (CRC)

and Block Character Checking

(BCC) for message validation.

Allen-Bradley protocol can use

CRC or BCC checking; Modicon

Modbus uses only CRC checking. Parity and Stop

Bit Selection:

Two jumpers allow selection of

parity and stop bit modes.

Specifications and Ordering InformationBCD Switch:

If set, the data returned in Allen-

Bradley protocol is formatted in

Binary Coded Decimal.

Data Format:

Up to 12-bit data is supported;

depends on monitor type.

Data Accuracy:

Data accuracy is the same as the

monitor (no additional losses). Dynamic Data Interface

Communications

Protocol:

Proprietary protocol for

communications with compatible

Bently Nevada computerized

monitoring systems. Connection

to computer is via RS422 (or

RS232 for rack closest to

computer). Data available via this

interface includes the following

on a per channel basis:

Proportional value for each

monitored variable available as

current values and a Fast Trend

file

Proportional value for probe gap

voltage (for proximity probe

channels)

OK status

Alert and Danger alarm status

Bypass status (channel and

monitor)

Trip Multiply status (rack)

Digitized dynamic waveform (time

domain) signals

Address Setting:

Uses the same eight jumpers on

the SDI.

Baud Rate:

Jumper-selectable; 38.k baud,

maximum.

Data Types:

All 3300 monitor types are

supported by DDI. Various types

of proportional data are obtained,

depending on monitor type,

including overall values, individual

channel alarm status, channel OK

status, probe gap (for proximity

probe based monitors), 1X and 2X

amplitude and phase (for vector

monitors).

Accuracy:

12-bit dynamic data is

maintained with no losses. While

DDI can support up to 24-bits of

resolution on static data, the

actual resolution is a function of

the monitor type for each

channel.

Dynamic Data:

12-bit dynamic data is obtained

2-channels at a time from all

3300 monitors which have

dynamic data.

Dynamic Data

Sampling -

Asynchronous:

Sampling rate is selected at the

host computer (Configuration

program); maximum rate is 12.8

kHz for maximum frequency

display (spectrum) of 5 kHz;

resolution 400 lines. Synchronous:

Sampling rate is fixed and is a

function of Keyphasor frequency

(shaft rotative speed). Maximum

Keyphasor frequency is 30,000

cpm (500 Hz). Dynamic data

signal is sampled 32 times per

shaft revolution (32X) for 8

revolutions; maximum frequency

12.5X, minimum 0.125X;

resolution 100 lines.

Trend Data:

Specifications and Ordering InformationSupports both a Trend and Fast

Trend for all proportional data. System Ok Relay

One hermetically sealed, normally

energized, single-pole double-

throw relay is used for

annunciation of a NOT OK

condition in the monitoring rack

and/or a problem with the

primary (mains) power to the rack. Contact Ratings

- Standard:

5A at 28 Vdc

5A at 120 Vac, 50/60 Hz

3A at 220 Vac, 50/60 Hz

CSA Approval:

5A at 28 Vdc

5A at 120 Vac, 50/60 Hz

ATEX approval:

5A at 28 Vdc

5A at 30 Vac, 50/60 Hz Ordering Information

System Monitor

3300/03-AXX-BXX

A: Type

0 1Standard

0 2 Serial Data Interface

0 3Dynamic Data Interface and

Serial Data Interface

B: Approvals Option

0 0 None

0 1 CSA/NRTL/C

0 2ATEX self certification

Note: ATEX approval requires the monitor

rack be installed in a weatherproof

housing.

Upgrade Kit 143121

0 1Basic to SDI upgrade

0 2 SDI to DDI upgrade

0 3Basic to DDI upgrade Accessories

Serial Data Interface Cables

RS232 3300/03 to Allen-Bradley 1770-KF2 Communication Module or Honeywell PLC® Gateway or Data Highway

968 - AXXXX-BXX-CXX

RS232 3300/03 to Allen-Bradley 1771-KE or 1785-KE Communications Module

969 - AXXXX-BXX-CXX

RS422 3300/03 to Allen-Bradley 1770 KF2 Communications Module

970 - AXXXX-BXX-CXX

A: Cable Length

0 0 1 0 10 feet (3 metres)

0 0 2 5 25 feet (7.5 metres)

0 0 5 0 50 feet (15 metres)

0 1 0 0100 feet (30 metres)

B: Assembly Option

0 1 Not Assembled

0 2Assembled

C: Protection Option

0 0No Surge Protection

0 1Surge Protection provided

RS422 3300/03 to 3300/03

47125 - AXXXX-BXX-CXX-DXX

A: Cable Length

0 0 1 010 feet (3 metres)

0 0 2 525 feet (7.5 metres)

0 0 5 050 feet (15 metres)

0 1 0 0100 feet (30 metres)

0 2 0 0200 feet (61 metres)

0 2 5 0250 feet (76 metres)

0 5 0 0500 feet (152 metres)

1 0 0 01000 feet (305 metres)

2 0 0 02000 feet (610 metres)*

4 0 0 04000 feet (1220 metres)* * Note: Can not be ordered assembled.

B: Assembly Option

0 1Not Assembled

0 2Assembled

C: Insulation Option

0 1PVC Insulated

0 2Teflon® Insulated

Specifications and Ordering Information

D: Protection Option

0 0No Surge Protection

0 1Surge Protection provided

RS422 3300/03 to 3300/01

(3300/01 electrically closest to host computer) 966 - AXXXX-BXX-CXX

RS422 3300/01 to 3300/03

(3300/03 electrically closest to host computer) 967 - AXXXX -BXX-CXX

A: Cable Length

0 0 1 010 feet (3 metres)

0 0 2 525 feet (7.5 metres)

0 0 5 050 feet (15 metres)

0 1 0 0100 feet (30 metres)

0 2 5 0250 feet (76 metres)

0 5 0 0500 feet (152 metres) B: Assembly Option

0 1Not Assembled

0 2Assembled

C: Surge Protection

0 0No Surge Protection

0 1Surge Protection Provided Dynamic Data Interface Cables

3300/03 to Bently Nevada host (DM2000) computer;

RS422

{9-pin female to 25-pin female}

132632 - AXXXX -BXX

(PVC Insulation)

132633 - AXXXX -BXX

(Teflon® Insulation)

A: Cable Length

0 0 1 010 feet (3 metres)

0 0 2 525 feet (7.5 metres)

0 0 5 050 feet (15 metres)

0 1 0 0100 feet (30 metres)

0 2 5 0250 feet (76 metres)

0 5 0 0500 feet (152 metres) B: Assembly Option

0 1Not Assembled

0 2Assembled

3300/03 to Bently Nevada host computer (IBM® compatible); RS232

949 - AXXXX-BXX-CXX 3300/03 to Bently Nevada host computer (Compaq or Intel); RS232

950 - AXXXX-BXX-CXX

A: Cable Length

0 0 1 010 feet (3 metres)

0 0 2 525 feet (7.5 metres)

0 0 5 050 feet (15 metres)

0 1 0 0100 feet (30 metres)

B: Assembly Option

0 1Not Assembled

0 2Assembled

C: Protection Option

0 0No Surge Protection

0 1Surge Protection Provided

3300/03 to Bently Nevada host (TDM2) computer; RS422 {9-pin female to 9-pin male}

103629 - AXXXX-BXX-CXX-DXX

A: Cable Length

0 0 1 010 feet (3 metres)

0 0 2 525 feet (7.5 metres)

0 0 5 050 feet (15 metres)

0 1 0 0100 feet (30 metres)

0 2 5 0250 feet (76 metres)

0 5 0 0500 feet (152 metres)

B: Assembly Option

0 1Not Assembled

0 2Assembled

C: Insulation Option

0 1PVC Insulated

0 2Teflon® Insulated

D: Protection Option

0 0No Surge Protection

0 1 Surge Protection provided

Surge Protector Kit

(for existing installations, not required when surge protection option is specified with new cables). 109959-AXX

(Note: Each communication cable requires one device at each end of the cable).

A: Surge Protector Kit

0 1TDM Comm Processor end

of cables 81650 and 78205

Specifications and Ordering Information0 2Host Computer end of TDM

cable 78205; both Host

and Comm Processor end

of DDI cable 950; Comm

Processor end of DDI cable

949.

0 3Host Computer end of TDM

cable 81650 and DDI cable

949.

0 4Comm Processor end of

cable 78206 (TDM Host to

First Comm Processor),

103629 (TDM2 Host to first

Comm Processor) and

132632 or 132633 (DM2000

Host to First Comm

Processor); both ends of

cable 47125 (DDM/PDM/

TDM Comm Processor to

Comm Processor); 3300/03

rack end of cables 966,

967, and 970.

0 5Host Computer end of

cable 78206 (TDM Host to

First Comm Processor).

0 6Host Computer end of

cable 103629 (TDM2 Host

to first Comm Processor). 0 7ost Computer end of

cables 132632 and 132633

(DM2000 Host to First

Comm Processor)

0 8llen-Bradley

Communications Module

end of cable 969

(3300/03 to Allen-Bradley

1771-KE).

0 9300/03 rack end of cables

968 (3300/03 to Allen-

Bradley 1770-KF2) and

969 (3300/03 to Allen-

Bradley 1771-KE).1 0

3300/01 rack end of cables

966 (3300/03 to 3300/01)

and, 967 (3300/03 to

3300/01) and on AB Comm

Module end of cable 970

(3300/03 to Allen-Bradley

Comm Module).

1 1Allen-Bradley

Communication Module

end of cable 968

(3300/03 to Allen-Bradley

1770-KF2).

Specifications and Ordering InformationField wiring diagrams

3300/03 System Monitor

Field wiring diagram for 3300/03 System Monitor

(ac Power Supply without internal barriers)

Specifications and Ordering InformationCable details

9-pin male Rack RS422 to 9-pin female Rack RS422

Figure 2: Part Number 949

Specifications and Ordering Information

Figure 3: Part Number 950

9-pin female Rack RS232 to 9-pin female Computer RS232

Figure 4: Part Number 966

9-pin female RS422 Rack cable to 25-pin male RS422 Rack cable

Specifications and Ordering Information

Figure 5: Part Number 967

9-pin male RS422 Rack cable to 25-pin female RS422 Rack cable

Figure 6: Part Number 968

9-pin female RS232 Rack to 25-pin female RS232 cable

Specifications and Ordering Information

Figure 7: Part Number 969

15-pin male RS232 cable to 9-pin female RS232 Rack cable

Figure 8: Part Number 970

Specifications and Ordering Information

Figure 9: Part Number 100058

Figure 10: Part Number 103629

9-pin male (P1) RS422 TDM2 Host cable to 9-pin female (J1-3300/03) RS422 Rack cable

Specifications and Ordering Information

Figure 11: Part Number 132632/132633

9-pin female RS422 Rack cable to 25-pin female RS422 DM2000 Host cable

Figure 12: Part Number 109959

Surge Protector

Specifications and Ordering InformationCopyright 2000. Bently Nevada LLC.

1631 Bently Parkway South, Minden, Nevada USA 423

Phone: 775.782.3611 Fax: 775.215.2873

www.ge-energy.com/bently

All rights reserved.

Bently Nevada, Keyphasor, and Proximitor are trademarks of General Electric Company.

Teflon is a trademark of E.I. duPont de Nemours & Company, Inc.

Modbus is a registered mark of Modicon Incorporated

PLC is a registered trademark of the Allen-Bradley Company, Inc.

™ PLC-5 and Data Highway Plus are trademarks of the Allen-Bradley Company, Inc.

IBM is a trademark of International Business Machines

Specifications and Ordering Information