Part Number 141524-01
Rev. F (04/07)
Description
The System Monitor performs four important tasks in a 3300 monitor rack, providing:
Functions common to all monitors in the rack, such as:
- Alarm setpoint adjustment
- Keyphasor ® power, termination, conditioning, and distribution - Alarm acknowledgement
Connection of all installed monitors to an external communications processor (sold separately) via STATIC and DYNAMIC data ports.
Optional Serial Data Interface (SDI) for communication of transducer and monitor data to process computers, digital/distributed control systems, programmable controllers, and other control and automation systems.
Optional Dynamic Data Interface (DDI) for communication of transducer and monitor data to compatible Bently Nevada machinery management software. Depending on the type of data required, this option may eliminate the need for an external communications processor.
Warning
A transducer field wiring failure, monitor failure, or loss of primary power can cause loss of machinery protection. This could result in property damage and/or bodily injury. Therefore, we strongly recommend connection of an external (operator control panel mounted) annunciator to the OK Relay terminals.
Inputs
Power
Consumption:
2 watts; 4.6 watts with interface
options.
Keyphasor
Signal:
Accepts up to four proximity
probe Keyphasor signals.
Input
impedance:
10 k Ω.
RS422
Communications
Impedance:
4 k Ω.
Threshold:
0.2 V.
Baud Rate:
19.2 k baud maximum for SDI;
38.4 k baud maximum for DDI. Distance:
1200 metres (4000 feet)
maximum.
RS232
Communications
Impedance:
3 k Ω to 7 k Ω.
Input Levels:
High +3 to +25 V;
Low -3 to -25V.
Baud Rate:
19.2 k baud maximum for
SDI and DDI.
Distance:
30 metres (100 feet) maximum. Keyphasor®
Signals Frequency
Range:
60 to 30,000 cpm (rpm).
Duty Cycle:
1% minimum.
Amplitude:
0.5 V peak-to-peak minimum.
dc Signal
Range:
0 to -24 V (VT = -24 Vdc);
0 to -18 V (VT = -18 Vdc).
Signal Conditioning
Frequency
Range:
Determined by software (user-
selectable); 10 kHz maximum. Accuracy -
Dynamic Signal:
± 0.3% of full-scale, typical, at
25°C (77°F);
±0.7% of full-scale, maximum, at
25°C (77°F).
Phase:
±0.2°, typical, at 25°C (77°F);
±1°, maximum, at 25°C (77°F). Gap:
0.3% of dc Signal Range, typical. RPM:
±1 rpm, typical.
Outputs
Buffered
Keyphasor
Outputs:
Four coaxial connectors on front
panel.
Output
Impedance:
100 Ω.
Specifications and Ordering InformationKeyphasor
Transducer
Power Supply:
User-programmable for -24 Vdc
or -18 Vdc. Voltages are short-
circuit protected.
Indicators:
Three LEDs on front panel Supplies OK:
ON when all system supply
voltages are within tolerance.
LEDs behind the slide-away front
panel indicate the condition of the
various monitored supply
voltages. The appropriate Supply
voltage LED and the SUPPLIES OK
LED on the front panel turn OFF if
a voltage is out of tolerance.
Trip Multiply:
ON when Trip Multiply function is
active.
Data Interface
OK:
OFF when either the SDI or the
DDI hardware is not functioning
properly or is not installed.
RS422
Communications
Levels:
High 2.5 V, minimum;
Low 0.5 V, maximum.
Baud Rate:
19.2 k baud, maximum, for SDI;
38.4 k baud, maximum, for DDI. Distance:
1200 metres (4000 feet),
maximum.
RS232
Communications
Levels:
High +5 V, minimum;
Low -5 V, maximum.
Baud Rate:
19.2 k baud, maximum,
for SDI and DDI.
Distance:
30 metres (100 feet), maximum. Controls
Front Panel:
Two switches control the Up and
Down adjustment of monitor
alarm setpoints. A third switch
controls the alarm RESET function. Rear Panel:
Terminals provide connections for
Rack Inhibit, Trip Multiply, and
Alarm Reset contact closures. Communications:
RS232 or RS422 communication
links. One connection to host
computer and one connection for
daisy chaining to the next rack. RS232 Interface:
150 baud to 19.2 k baud; 30
metres (100 feet) maximum.
RS422 Interface:
150 baud to 19.2 k baud for SDI;
150 baud to 38.4 k baud for DDI;
1200 metres (4,000 feet)
maximum.
Environmental Limits
Operating
Temperature:
0°C to +65°C (+32°F to +150°F). Storage
Temperature:
-40°C to +85°C (-40°F to +185°F). Relative
Humidity:
To 95%, noncondensing.
EMC Directive
Certificate of
Conformity:
158710
Specifications and Ordering InformationLow Voltage
Directive
Certificate of
Conformity:
135300
Hazardous Area Approvals
Approval Option
(01)
Class I, Div 2
Groups A, B, C, D
T4 @ Ta = -20 °C to +65 °C
(-4 °F to +150 °F)
Certification
Number
CSA 150368-1002151 (LR 26744) ATEX
Approval Option
(02)
For Selected Ordering Options
with ATEX/CSA agency
approvals:
II G
EEx nC[L] IIC
T4 @ Ta = -20°C to +60°C Certification
Number
BN26744C-55A
Physical
Rack Space
Requirements:
One rack position, installs only in
position two (next to the Power
Supply).
Weight:
0.9 kg (2.2 lbs.). Communications
Protocol:
Either Modicon Modbus® or
Allen-Bradley DF1 protocol (switch
selectable); RS422 or RS232
cabling (jumper-selectable). Data
available via this interface
includes the following on a per
channel basis:
Proportional value for each
monitored variable (available as
current values and a Fast Trend
file)
Proportional value for probe gap
voltage (for proximity probe
channels)
OK status
Alert and Danger alarm status
Bypass status (channel and
monitor)
Trip Multiply status (rack)
Monitor alarm setpoints (Modicon
Modbus only)
Address Setting:
Eight jumpers on the Serial Data
Interface allow setting of up to
256 different addresses.
Baud Rate:
Four jumpers are used to set the
desired baud rate for serial
communications; 19.2 k baud,
maximum.
Message
Checking:
One jumper selects between
Cyclic Redundancy Check (CRC)
and Block Character Checking
(BCC) for message validation.
Allen-Bradley protocol can use
CRC or BCC checking; Modicon
Modbus uses only CRC checking. Parity and Stop
Bit Selection:
Two jumpers allow selection of
parity and stop bit modes.
Specifications and Ordering InformationBCD Switch:
If set, the data returned in Allen-
Bradley protocol is formatted in
Binary Coded Decimal.
Data Format:
Up to 12-bit data is supported;
depends on monitor type.
Data Accuracy:
Data accuracy is the same as the
monitor (no additional losses). Dynamic Data Interface
Communications
Protocol:
Proprietary protocol for
communications with compatible
Bently Nevada computerized
monitoring systems. Connection
to computer is via RS422 (or
RS232 for rack closest to
computer). Data available via this
interface includes the following
on a per channel basis:
Proportional value for each
monitored variable available as
current values and a Fast Trend
file
Proportional value for probe gap
voltage (for proximity probe
channels)
OK status
Alert and Danger alarm status
Bypass status (channel and
monitor)
Trip Multiply status (rack)
Digitized dynamic waveform (time
domain) signals
Address Setting:
Uses the same eight jumpers on
the SDI.
Baud Rate:
Jumper-selectable; 38.k baud,
maximum.
Data Types:
All 3300 monitor types are
supported by DDI. Various types
of proportional data are obtained,
depending on monitor type,
including overall values, individual
channel alarm status, channel OK
status, probe gap (for proximity
probe based monitors), 1X and 2X
amplitude and phase (for vector
monitors).
Accuracy:
12-bit dynamic data is
maintained with no losses. While
DDI can support up to 24-bits of
resolution on static data, the
actual resolution is a function of
the monitor type for each
channel.
Dynamic Data:
12-bit dynamic data is obtained
2-channels at a time from all
3300 monitors which have
dynamic data.
Dynamic Data
Sampling -
Asynchronous:
Sampling rate is selected at the
host computer (Configuration
program); maximum rate is 12.8
kHz for maximum frequency
display (spectrum) of 5 kHz;
resolution 400 lines. Synchronous:
Sampling rate is fixed and is a
function of Keyphasor frequency
(shaft rotative speed). Maximum
Keyphasor frequency is 30,000
cpm (500 Hz). Dynamic data
signal is sampled 32 times per
shaft revolution (32X) for 8
revolutions; maximum frequency
12.5X, minimum 0.125X;
resolution 100 lines.
Trend Data:
Specifications and Ordering InformationSupports both a Trend and Fast
Trend for all proportional data. System Ok Relay
One hermetically sealed, normally
energized, single-pole double-
throw relay is used for
annunciation of a NOT OK
condition in the monitoring rack
and/or a problem with the
primary (mains) power to the rack. Contact Ratings
- Standard:
5A at 28 Vdc
5A at 120 Vac, 50/60 Hz
3A at 220 Vac, 50/60 Hz
CSA Approval:
5A at 28 Vdc
5A at 120 Vac, 50/60 Hz
ATEX approval:
5A at 28 Vdc
5A at 30 Vac, 50/60 Hz Ordering Information
System Monitor
3300/03-AXX-BXX
A: Type
0 1Standard
0 2 Serial Data Interface
0 3Dynamic Data Interface and
Serial Data Interface
B: Approvals Option
0 0 None
0 1 CSA/NRTL/C
0 2ATEX self certification
Note: ATEX approval requires the monitor
rack be installed in a weatherproof
housing.
Upgrade Kit 143121
0 1Basic to SDI upgrade
0 2 SDI to DDI upgrade
0 3Basic to DDI upgrade Accessories
Serial Data Interface Cables
RS232 3300/03 to Allen-Bradley 1770-KF2 Communication Module or Honeywell PLC® Gateway or Data Highway
968 - AXXXX-BXX-CXX
RS232 3300/03 to Allen-Bradley 1771-KE or 1785-KE Communications Module
969 - AXXXX-BXX-CXX
RS422 3300/03 to Allen-Bradley 1770 KF2 Communications Module
970 - AXXXX-BXX-CXX
A: Cable Length
0 0 1 0 10 feet (3 metres)
0 0 2 5 25 feet (7.5 metres)
0 0 5 0 50 feet (15 metres)
0 1 0 0100 feet (30 metres)
B: Assembly Option
0 1 Not Assembled
0 2Assembled
C: Protection Option
0 0No Surge Protection
0 1Surge Protection provided
RS422 3300/03 to 3300/03
47125 - AXXXX-BXX-CXX-DXX
A: Cable Length
0 0 1 010 feet (3 metres)
0 0 2 525 feet (7.5 metres)
0 0 5 050 feet (15 metres)
0 1 0 0100 feet (30 metres)
0 2 0 0200 feet (61 metres)
0 2 5 0250 feet (76 metres)
0 5 0 0500 feet (152 metres)
1 0 0 01000 feet (305 metres)
2 0 0 02000 feet (610 metres)*
4 0 0 04000 feet (1220 metres)* * Note: Can not be ordered assembled.
B: Assembly Option
0 1Not Assembled
0 2Assembled
C: Insulation Option
0 1PVC Insulated
0 2Teflon® Insulated
Specifications and Ordering Information
D: Protection Option
0 0No Surge Protection
0 1Surge Protection provided
RS422 3300/03 to 3300/01
(3300/01 electrically closest to host computer) 966 - AXXXX-BXX-CXX
RS422 3300/01 to 3300/03
(3300/03 electrically closest to host computer) 967 - AXXXX -BXX-CXX
A: Cable Length
0 0 1 010 feet (3 metres)
0 0 2 525 feet (7.5 metres)
0 0 5 050 feet (15 metres)
0 1 0 0100 feet (30 metres)
0 2 5 0250 feet (76 metres)
0 5 0 0500 feet (152 metres) B: Assembly Option
0 1Not Assembled
0 2Assembled
C: Surge Protection
0 0No Surge Protection
0 1Surge Protection Provided Dynamic Data Interface Cables
3300/03 to Bently Nevada host (DM2000) computer;
RS422
{9-pin female to 25-pin female}
132632 - AXXXX -BXX
(PVC Insulation)
132633 - AXXXX -BXX
(Teflon® Insulation)
A: Cable Length
0 0 1 010 feet (3 metres)
0 0 2 525 feet (7.5 metres)
0 0 5 050 feet (15 metres)
0 1 0 0100 feet (30 metres)
0 2 5 0250 feet (76 metres)
0 5 0 0500 feet (152 metres) B: Assembly Option
0 1Not Assembled
0 2Assembled
3300/03 to Bently Nevada host computer (IBM® compatible); RS232
949 - AXXXX-BXX-CXX 3300/03 to Bently Nevada host computer (Compaq or Intel); RS232
950 - AXXXX-BXX-CXX
A: Cable Length
0 0 1 010 feet (3 metres)
0 0 2 525 feet (7.5 metres)
0 0 5 050 feet (15 metres)
0 1 0 0100 feet (30 metres)
B: Assembly Option
0 1Not Assembled
0 2Assembled
C: Protection Option
0 0No Surge Protection
0 1Surge Protection Provided
3300/03 to Bently Nevada host (TDM2) computer; RS422 {9-pin female to 9-pin male}
103629 - AXXXX-BXX-CXX-DXX
A: Cable Length
0 0 1 010 feet (3 metres)
0 0 2 525 feet (7.5 metres)
0 0 5 050 feet (15 metres)
0 1 0 0100 feet (30 metres)
0 2 5 0250 feet (76 metres)
0 5 0 0500 feet (152 metres)
B: Assembly Option
0 1Not Assembled
0 2Assembled
C: Insulation Option
0 1PVC Insulated
0 2Teflon® Insulated
D: Protection Option
0 0No Surge Protection
0 1 Surge Protection provided
Surge Protector Kit
(for existing installations, not required when surge protection option is specified with new cables). 109959-AXX
(Note: Each communication cable requires one device at each end of the cable).
A: Surge Protector Kit
0 1TDM Comm Processor end
of cables 81650 and 78205
Specifications and Ordering Information0 2Host Computer end of TDM
cable 78205; both Host
and Comm Processor end
of DDI cable 950; Comm
Processor end of DDI cable
949.
0 3Host Computer end of TDM
cable 81650 and DDI cable
949.
0 4Comm Processor end of
cable 78206 (TDM Host to
First Comm Processor),
103629 (TDM2 Host to first
Comm Processor) and
132632 or 132633 (DM2000
Host to First Comm
Processor); both ends of
cable 47125 (DDM/PDM/
TDM Comm Processor to
Comm Processor); 3300/03
rack end of cables 966,
967, and 970.
0 5Host Computer end of
cable 78206 (TDM Host to
First Comm Processor).
0 6Host Computer end of
cable 103629 (TDM2 Host
to first Comm Processor). 0 7ost Computer end of
cables 132632 and 132633
(DM2000 Host to First
Comm Processor)
0 8llen-Bradley
Communications Module
end of cable 969
(3300/03 to Allen-Bradley
1771-KE).
0 9300/03 rack end of cables
968 (3300/03 to Allen-
Bradley 1770-KF2) and
969 (3300/03 to Allen-
Bradley 1771-KE).1 0
3300/01 rack end of cables
966 (3300/03 to 3300/01)
and, 967 (3300/03 to
3300/01) and on AB Comm
Module end of cable 970
(3300/03 to Allen-Bradley
Comm Module).
1 1Allen-Bradley
Communication Module
end of cable 968
(3300/03 to Allen-Bradley
1770-KF2).
Specifications and Ordering InformationField wiring diagrams
3300/03 System Monitor
Field wiring diagram for 3300/03 System Monitor
(ac Power Supply without internal barriers)
Specifications and Ordering InformationCable details
9-pin male Rack RS422 to 9-pin female Rack RS422
Figure 2: Part Number 949
Specifications and Ordering Information
Figure 3: Part Number 950
9-pin female Rack RS232 to 9-pin female Computer RS232
Figure 4: Part Number 966
9-pin female RS422 Rack cable to 25-pin male RS422 Rack cable
Specifications and Ordering Information
Figure 5: Part Number 967
9-pin male RS422 Rack cable to 25-pin female RS422 Rack cable
Figure 6: Part Number 968
9-pin female RS232 Rack to 25-pin female RS232 cable
Specifications and Ordering Information
Figure 7: Part Number 969
15-pin male RS232 cable to 9-pin female RS232 Rack cable
Figure 8: Part Number 970
Specifications and Ordering Information
Figure 9: Part Number 100058
Figure 10: Part Number 103629
9-pin male (P1) RS422 TDM2 Host cable to 9-pin female (J1-3300/03) RS422 Rack cable
Specifications and Ordering Information
Figure 11: Part Number 132632/132633
9-pin female RS422 Rack cable to 25-pin female RS422 DM2000 Host cable
Figure 12: Part Number 109959
Surge Protector
Specifications and Ordering InformationCopyright 2000. Bently Nevada LLC.
1631 Bently Parkway South, Minden, Nevada USA 423
Phone: 775.782.3611 Fax: 775.215.2873
www.ge-energy.com/bently
All rights reserved.
Bently Nevada, Keyphasor, and Proximitor are trademarks of General Electric Company.
Teflon is a trademark of E.I. duPont de Nemours & Company, Inc.
Modbus is a registered mark of Modicon Incorporated
PLC is a registered trademark of the Allen-Bradley Company, Inc.
™ PLC-5 and Data Highway Plus are trademarks of the Allen-Bradley Company, Inc.
IBM is a trademark of International Business Machines
Specifications and Ordering Information