Common numbering of IEC 62271 publications falling under the responsibility of subcommittees SC 17A and SC. 17c
| IEC 62271 series | HIGH-VOLTAGE SWITCHGEAR AND CONTROLGER 高压开关设备和控制设备 | Old IEC number if any |
| part | New title | |
| 1 | Common specifications 通用说明 | IEC 60694 |
| 2 | Seismic qualification for rated voltages of 72.5Kv and above 72.5kV及以上设备抗地震性能 | - |
| 100 | High-voltage alternating current circuit-breakers 高压交流断路器 | IEC 60056 |
| 101 | Synthetic testing 合成测试 | IEC 60427 |
| 102 | High-voltage alternating current disconnections and earthing switches 高压交流隔离开关和接地开关 | IEC 60129 |
| 103 | Switches for rated voltages above 1kV and less than 52kV 1kV~52kV的开关设备 | IEC 60265-1 |
| 104 | Switches for rated voltages of 52 kV and above 52kV及以上的高压开关设备 | IEC 60265-2 |
| 105 | Alternating current switch-fuse combinations 高压交流开关-熔断器组合 | IEC 60420 |
| 106 | Alternating current contactors and contactor-based motor-starters 交流接触器和 | IEC 60470 |
| 107 | Alternating current switchgear-fuse combinations 高压交流开关设备-熔断器组合 | - |
| 108 | Switchgear having combined function 开关设备的联动功能 | - |
| 109 | Series capacitor by-pass switches 串连电容器 | - |
| 200 | AC metal-enclosed switchgear and control gear for rated voltage above 1kV and up to and including 52 kV 1kV~52 kV 交流金属封闭开关和控制设备 | IEC 60298 |
| 201 | Insulation-enclosed switchgear and controlgear for rated voltage up to and including 52 kV 52 kV及以上绝缘封闭开关设备 | IEC 60466 |
| 202 | High-voltage/ Low-voltage prefabricated substations 高低压箱式变电站 | IEC 61330 |
| 203 | Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV 额定电压在52 kV以上气体绝缘金属封闭开关设备 | IEC 60517 |
| 204 | High-voltage gas-insulated transmission lines for rated voltages of 72.5 kV and above 额定电压在72.5 kV及以上高压气体绝缘输电线路 | IEC 610 |
| (300) | Guide for seismic qualification of high-voltage alternating current circuit-breakers 高压交流断路器地震条件导则 | IEC 61166 |
| (301) | Guide for inductive load switching感应负载开关导则(高压交流断路器) | IEC 61223 |
| (302) | Guide for short-circuit and switching test procedures for metal-enclosed and dead tank circuit-breakers 金属封闭和落地罐式断路器的短路和开合试验程序导则 | IEC 61633 |
| (303) | Use and handling of sulphur hexafluoride (SF6) in high-voltage switchgear and controlgear 高压开关和控制设备种SF6的使用和操作 | IEC 61634 |
| (304) | Additional requirements for enclosed switchgear and controlgear from 1 kV to 72.5 kV to be used in severs climatic conditions 1 kV 到 72.5 kV封闭开关和控制设备用在特殊环境条件下的附加要求 | IEC 60932 |
| (305) | Cable connections for gas-insulated metal-enclosed switchgear for rated voltages above 52 kV. 52 kV及以上气体绝缘金属封闭开关设备的电缆连接 | IEC 60859 |
| (306) | Direct connection between power transformers and gas-insulated metal-enclosed switchgear for rated voltages above 52 kV. 52 kV及以上发电机变压器和气体绝缘金属封闭开关设备的直接连接 | IEC 61639 |
| (307 | Use of electronic and associated technologies in auxiliary equipment of switchgear and controlgear 开关设备和控制设备的辅助设备种电气和相关技术的使用 | IEC 62063 |
| (308) | Guide for asymmetrical short-circuit breaking test duty T 100a 非对称短路开端试验导则 | - |
| (309) | TRV parameters for high-voltage switchgear and controlgear for rated voltages above l kV and less than 100 kV. | - |
| (310) | Electrical endurance testing for circuit-breakers rated 72.5 kV and above 72.5 kV及以上的断路器的电动力续性试验 | - |
Table 102-Preferred rated insulation levels for rated voltages
for equipment of range 1
Rated voltage for equipment
Ur
kV (r.m.s.value)
| 设备额定电压 | Rated short-duration power-frequency withstand voltage (额定短时工频耐受电压) Ud kV (r.m.s.value) | Rated lightning impulse withstand voltage (额定雷电冲击耐受电压) Up kV(peckvalue) | ||
| Phase-to-earth, across open switching device and between phase 相对地,相间和通过断开的设备 | Across the isolating distance 通过的绝缘距离 | Phase-to-earth, across open switching device and between phase 相对地,相间和通过断开的设备 | Across the isolating distance 通过的绝缘距离 | |
| (1) | (2) | (3) | (4) | (5) |
| 72.5 | 140 | 160 | 325 | 375 |
| 100 | 185 | 210 | 450 | 520 |
| 123 | 230 | 265 | 550 | 630 |
| 145 | 275 | 315 | 650 | 750 |
| 170 | 325 | 375 | 750 | 860 |
| 245 | 460 | 530 | 1050 | 1200 |
| NOTE Values in column(2) are applicable A)For type tests, phase-to-earth and between phases; B)For routine tests, phase-to-phase, and across the open switching device. Values in columns(3), (4) and (5) are applicable for type tests only. 注意:第二列的电压用于: (1)相对地和相间的测试类型 (2)第三、四、五列种的电压值仅适用于相对地,相间和通过断开的开关设备的常规测试, | ||||
Table 103-Preferred rated insulation levels for rated voltages
for equipment of range II
Rated voltage for equipment
Ur
kV (r.m.s.value)
| 设备额定电压 | Rated short-duration power-frequency withstand voltage (额定短时工频耐受电压) Ud kV (r.m.s.value) | Rated switching impulse withstand voltage (额定开关冲击耐受电压) Us kV (r.m.s.value) | Rated lightning impulse withstand voltage (额定雷电冲击耐受电压) Up kV(peckvalue) | ||||
| Phase-to-earth, and between phase (note 3) 相对地和相间 | across open switching device and /or isolating distance (note 3) | Phase-to-earth, and across open switching device 相对地和相间 | between phase (note 4) 相间 | Across isolating distance (note 1,2 and 3) 通过绝缘距离 | Phase-to-earth, and between phase 相对地和相间 | across open switching device and /or isolating distance (note 3) 通过断开的开关设备和/或绝缘距离 | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| 300 | 460 | 595 | 850 | 1275 | 700(+245) | 1050 | 1050(+170) |
| 362 | 520 | 675 | 950 | 1425 | 800(+295) | 1175 | 1175(+205) |
| 420 | 650 | 815 | 1050 | 1575 | 900(+345) | 1425 | 1425(+240) |
| 550 | 710 | 925 | 1175 | 1760 | 900(+450) | 1550 | 1550(+315) |
| 800 | 960 | 1270 | 1425 | 2420 | 1100(+650) | 2100 | 2100(+453) |
| NOTE 1 column (6) is also applicable to some circuit-breakers, see IEC 62271-100. NOTE 2 in column (6) , values in brackets are the peck values of the power-frequency voltage Ur/√2/ √3 applied to the opposite terminal (combined voltage) In column (8), value in brackets are the peck values of the power-frequency voltage 0.7 Ur/√2/ √3 applied to the opposite terminal (combined voltage).see annex D of IEC 60694. NOTE(3) Values in column(2) are applicable: (a)for type tests ,phase-to-earth and between phases; (b)for routine tests, phase-to-earth, phase-to-phase, and across the open switching device. Values in columns(3), (4), (5), (6), (7) and (8) are applicable for type tests only. NOTE(4) these values are derived using the multiplying factors stated in Table 3 of IEC 60070-1(1993) 注1:第6列也适用于一些断路器,参见IEC 62271-100. 注2:在第6列,括号内的数字是加在同一极相应端子上的反极性工频电压的峰值。 注3:第二列种的数字适用于: 相间试验类型 相对地,相间和通过断开的开关设备间的常规测试 (3), (4), (5), (6), (7)和 (8) 列种的数值仅用于典型测试 注4: | |||||||