数据和系统状态
Valve Regulated Lead Acid Batteries
Historical Data and System Status
Company(公司) | System Float Changing Vollage(系统浮充电压) VDC |
Location(地点) | Late Batteries Installed(电池安装日期) |
Supervisor in Charge(充电程序) Phone(电话) | Load(K.W.or Ampere)(负载K.W.或安装日期) |
Type CHARGER/Load(充电机/负载类型) | System Equalize Voltage(系统均充电压) VDC |
Unit Part Number(单元编号): Cells Unit(每单元室数) | Room Temperature(室温): ℃ Unit Temperature Rang: |
日期 | Date 日期 | ||||||||
Unit 单元 NO. 编号 | ChargingVolts -nit 单元充电电压 | Impedance (阻抗) Conductance (传导率) 交流毫伏 | 10Sec.Vmin@100Amps.(100A10秒)(放电最低电压 | Connection Resisace (连接电抗) | Unit 单元 NO. 编号 | Charging Volts-Unit 单元充电 电压 | Impedance (阻抗) Conductance (传导率) 交流毫伏 | 10Sec.Vmin@100Amps.(100A10秒)(放电最低电压 | Connection Resisace (连接电抗) |
1 | 9.8V | 11 | 0 | ||||||
2 | 9.6V | 12 | 0.68 | ||||||
3 | 11.2V | 13 | 0.74 | ||||||
4 | 11.8V | 14 | 6.3 | ||||||
5 | 9.3V | 15 | 6.5 | ||||||
6 | 7.2 | 16 | 11.3 | ||||||
7 | 11.8 | 17 | 10.9 | ||||||
8 | 12.2 | 18 | 8.3 | ||||||
9 | 12.1 | 19 | 9.7 | ||||||
10 | 11.3 | 20 | 12.2 | ||||||
21 | 12.2 | 31 | 0.16 | ||||||
22 | 12.2 | 32 | 2.3 | ||||||
23 | 11.8 | 33 | 4.7 | ||||||
24 | 11.3 | 34 | 5.2 | ||||||
25 | 9.8 | 35 | 11.2 | ||||||
26 | 11.3 | 36 | 11.7 | ||||||
27 | 0.63 | 37 | 0.98 | ||||||
28 | 9.3 | 38 | 8.9 |
29 | 9.7 | 39 | 10.2 | ||||||
30 | 9.8 | 40 | 11.3 |
测!
ROMM VISUAL CHECKS(室内目视检查): 室内温度及环境不满足要求,主
机周遍的空间太下,散热不量,缩短了设备的使用寿命。
BATTERY VISUAL CHECKS(电池目视检查): 电池外观灰尘较多 !