3.5 A wire or cable for Class 2 use shall have a voltage rating less than or equal to 150 V AC or DC.
2.新增4.3内容:由于可能不兼容性,裸铜,铜合金,铜包铝,铜包钢或其他最外层是裸铜
不应该和铝直接表面接触。可以接受隔离层来避免直接接触,或铜材质需要被镀层。
4.3 Due to possible incompatibility, uncoated copper, copper alloy, copper-clad aluminum, copper-cladsteel, or other components with uncoated copper on the outer surface shall not be used in wire or cablewhereby direct contact with aluminum may occur. A separator is one acceptable means of avoiding directcontact, or the copper components shall be metal-coated.
3.新增表5.2
4修订5.3.1,新增实心导体不能大于表5.1下一个AWG导体大小
5.修订5.3.3,新增绞合导体截面积不大于表5.1下一个AWG导体大小
6.新增
5.3.4 For a conductor composed of minimum 97 percent IACS unalloyed copper described in the
Exception to 51.2(f) the determination of conductor resistance described in 5.6.1 – 5.6.3 may be used as an alternative method for determining conductor size and, in the case of a dispute, shall be used as the referee method of determining conductor size
7.新增5.3.5
5.3.5 5.3.5 For a conductor composed of a material other than minimum 97 percent IACS unalloyed copperdescribed in the Exception to , the determination of conductor resistance described in 5.6.1 – 5.6.3shall be conducted.. 除了在例51.2(f)描述的最小97%的IACS非合金铜外,导体阻抗取决于5.6.1—5.6.3.。
8.新增5.3.6
5.3.6 For a tinsel conductor, the determination of the conductor resistance marked on the tag [see
48.2(e)] shall be conducted in accordance with UL 1581, Section 220.
对于箔导体,在标签上标注的导体电阻参照UL1581 220节。
9.更改导体的绞距。绞距以前只规定了铜导体,现新增了铜合金,铜包钢,铝,铜包铝。
10.新增以下表格:
11 新增半导电聚合层的定义
5.9.1半导电聚合层可以由一个或多个导体组成。
5.9.2去掉绝缘聚合层能很清楚和导体识别出来,颜色不能是绿或绿/黄。层是实心的,条状或其他的形状。
12.修改7.3.1,7.3.2,对于平均厚度小于0.05mm,测试值要精确到0.0025mm.
11.修订11.3、11.4,裸铜或铜合金地线不能和铝箔面接触。
12.新增12.2,对于CABLE由不同电压等级的芯线组成,CABLE的电压等级不能大于
绝缘芯线的最低等级,芯线的电压印字也应和CABLE一致。
12.2 Insulated conductors with different voltage ratings that are mixed in a given cable complies with the intent of this requirement when the cable is rated for not higher than the lowest voltage rating of any of the constituent insulated conductors. When the insulated conductors are marked with a voltage rating, the voltage rating shall be the same as that of the finished cable
13.修订50.3,对于含导电聚合屏蔽的CABLE,CABLE表面或标示带应该印″Conductive Shield,″″Contains Polymeric Conductive Shield, CABLE表面印字间距不超过1M. marker tape 不超过0.635M
14.修订51(标签副卡)
15.新增IEC 60332-1 Flame Test(≥20AWG)及 IEC 60332-2 Flame Test(小于20AWG)燃烧等级。
为了评定线缆的阻燃性能优劣,国际电工委员会分别制定了IEC60332-1、IEC60332-2和IEC60332-3三个标准。IEC60332-1和IEC60332-2分别用来评定单根线缆按倾斜和垂直布放时的阻燃能力(国内对应GB12666.3和GB12666.4标准)。IEC60332-3(国内对应GB12666.5-90)用来评定成束线缆垂直燃烧时的阻燃能力,相比之下成束线缆垂直燃烧时在阻燃能力的要求上要高得多。
IEC60332-1/BS4066-1阻燃等级(单根电线或电缆垂直燃烧测试FlameTestONSingleVerticalInsulatedWires/Cables)
这是单根电缆的阻燃标准。试验规定,一根60cm长的试样垂直固定在前壁开通的金属箱内,火焰长度175mm的丙烷燃烧器从距试样的上部固定端450mm的位置上火焰锥和电缆以45度角接触,如果试样燃烧损坏部分距离固定端下部不超过50mm,测试通过。 IEC60332-3/BS4066-3阻燃等级(成束电线或电缆垂直燃烧测试FlameTestOnBunchedWires/Cables)
这是成束电缆的阻燃标准。试验规定,成束3.5m长的电缆试样用铁丝固定在梯形测试架上,试样数量按不同分类所要求的非金属物料决定。试样垂直挂在燃烧炉背壁上,空气通过底板上的进气口引入燃烧炉。
丙烷平面燃烧器以750℃的火焰和试样接触,试样在强制吹风(气流排放5m3/分钟,风速0.9m/秒)的情况下,必须在垂直燃烧20分钟内燃不起来,电缆在火焰蔓延2.5米以内自行熄灭。IEC60332有A类、B类、C类和D类之分,以评定阻燃性能优劣。[2]