最新文章专题视频专题问答1问答10问答100问答1000问答2000关键字专题1关键字专题50关键字专题500关键字专题1500TAG最新视频文章推荐1 推荐3 推荐5 推荐7 推荐9 推荐11 推荐13 推荐15 推荐17 推荐19 推荐21 推荐23 推荐25 推荐27 推荐29 推荐31 推荐33 推荐35 推荐37视频文章20视频文章30视频文章40视频文章50视频文章60 视频文章70视频文章80视频文章90视频文章100视频文章120视频文章140 视频2关键字专题关键字专题tag2tag3文章专题文章专题2文章索引1文章索引2文章索引3文章索引4文章索引5123456789101112131415文章专题3
当前位置: 首页 - 正文

新冷干机使用说明书(中英文)

来源:动视网 责编:小OO 时间:2025-09-27 21:38:43
文档

新冷干机使用说明书(中英文)

SLAD系列操作使用说明书购买日期型号出厂编号目录一、冷干机原理………………………………………………………………………2二、冷干机零部件图解………………………………………………………………3三、设备安装事项…………………………………………………………………4-6四、SLAD系列冷冻式干燥机操作方法…………………………………………6-7五、常规控制仪表板说明……………………………………………………………7六、冷干机的启动过程………………………………………………………………8七、冷干机的停机过程…
推荐度:
导读SLAD系列操作使用说明书购买日期型号出厂编号目录一、冷干机原理………………………………………………………………………2二、冷干机零部件图解………………………………………………………………3三、设备安装事项…………………………………………………………………4-6四、SLAD系列冷冻式干燥机操作方法…………………………………………6-7五、常规控制仪表板说明……………………………………………………………7六、冷干机的启动过程………………………………………………………………8七、冷干机的停机过程…
SLAD系列

操作使用说明书

购买日期
型号
出厂编号
  

目录

一、冷干机原理………………………………………………………………………2

二、冷干机零部件图解………………………………………………………………3

三、设备安装事项…………………………………………………………………4-6

四、SLAD系列冷冻式干燥机操作方法…………………………………………6-7

五、常规控制仪表板说明……………………………………………………………7

六、冷干机的启动过程………………………………………………………………8

七、冷干机的停机过程………………………………………………………………8

八、冷干机的保养要求…………………………………………………………9-10

九、冷干机的典型故障分析和处理……………………………………………11-14

  

冷干机工艺流程

冷干机配置流程

冷干机主要零部件图解

设备安装注意事项

一、冷干机安装标准要求:无须安装地脚螺栓,但要求基础水平坚固,并要顾及排水系统的高度

和设置排水地沟。二、冷干机避免安置于屋外直接日晒和雨淋或温度高、通风不良以及尘埃多的场所,需安装在环

境温度高于0℃低于38℃的地方,风冷式冷干机必须安置在室内,并具有良好的通气设备以

维持冷干机的正常工作。安装在空压房内的风冷式冷干机,要采取冷干机与空压机的隔热措

施。

将风冷冷干机置于可使冷却空气便于通过冷凝器的地方,设备与周围环境或机器之间的距离应保持在1米以上的空间便于保养和维修。

三、安装时应尽量避免管道太长,弯曲角度太多,管径太小,以免产生压力降,设备空气进出口口上方请加装旁路阀以利检修。

四、安装冷干机电源时电器接线可能在运输过程中由于震动而松动,请用工具拧紧,并注意以下几点:  1、额定电压在±5%范围以内。  2、电源进线的线径须视电流大小及线路长短而定。  3、SLAD-0.5NF∽8.5NF电源须专用。

五、水冷型的冷干机,循环冷却水的水压须在0.2-0.4Mpa之间,水温≤32℃且经过软化处理,为防止水冷冷凝器生锈或脏堵,建议在水冷冷凝器的冷却水进口安装水过滤器。

六、冷干机入口处最好加装主管路过滤器,可避免冷干机的换热管表面被≥3um的固态杂质和油雾污染,直接影响冷干机的热交换性能。

七、冷干机最好装在后部冷却器与储气罐之后,以降低压缩空气在冷干机的进口温度,关系机体的性能及寿命,请妥善处理,如有疑难,欢迎致电询问。

电子排水器的安装和使用

一、过滤球阀集隔离用球阀和过滤网于一体,外形小巧,清洗方便;额定压力16Bar,冷凝水入口1/2",出口1/2"或1/4"。加装在电子排水器之前,确保阀芯不易堵塞(如下图示)。

二、电磁阀安装时须注意冷凝水的流动方向应该与阀体上箭头的方向一致;阀体水平位置安装,线圈朝上;阀的出口处连接管子(如硬PVC管)并通入下水道。

三、定时器接线时先拧下接线头顶部的螺丝,从定时器上拔下接线头,取下接线头的外壳(接线头盖),把连接电缆线从外壳穿线孔穿过,如下图所示进行接线。接线完毕后,将接线头盖装回原处,将接线头重新插到定时器上,收紧电缆线,适度拧紧接线头盖的防水螺母,防止潮气沿电缆线进入定时器,最后再拧紧固定螺丝(十字头M3)。此螺丝除了有连接作用外,更有压紧密封垫的功能,防止水进入密封垫的结合部,因此务必拧紧,否则,密封垫起不到防水作用,会造成线圈及定时器的故障。

 

四、设定定时器时,用左边旋钮设定间隔时间,用右边旋钮设定排放时间,用户应根据气候及工况做调整。

SLAD系列冷冻式干燥机操作方法 

一、开机前的检查

1. 检查制冷系统:观察设备仪表板上的冷媒高、低压表读数,两表在一定压力下达到平衡,而这平衡压力是根据周围温度的高低而上下波动,一般在(0.5MPa左右~1.2MPa左右)。

 

  2. 检查电源电压是否正常,(SLAD-0.5NF~SLAD-8.5NF为AC220V/50HZ±5%;SLAD-10NF以上为3相AC380/220V/50HZ±5%)。

3. 检查空气管路是否正常,空气进口压力不得超过选型时的工作压力,进气温度尽量不超过选型时的确定值。

4.  处理量30立方及以上的冷干机装有压缩机油加热器,在设备首次使用开机前必须加热(接通电源,加热器自动加热)8小时以上,以保证压缩机油腔内的油温至少高于环境温度10℃,否则,压缩机将会严重损毁。

5.  若选用的是水冷式,还应检查冷却水是否已经接至冷凝器,冷却水是否正常,水压为0.2Mpa~0.4Mpa,水温≤32℃。

常规控制仪表板说明

冷媒低压表(压力露点表):指示蒸发器内冷媒的饱和压力值。冷媒高压表:指示冷媒的冷凝压力值。空气出口压力表:指示压缩空气在冷干机出口处的压力值。

转换开关(黑色旋钮):就地/远程控制转换。

待启动指示灯(绿):按下启动按钮后此灯亮,5分钟后压缩机启动后暗掉。启动按钮(绿):按下按钮,则冷干机被接通电源开始运转工作。

停机按钮(红):按下此按钮则冷干机停止工作。电源指示灯(红):电源接通合上空气开关后此灯亮。运行指示灯(绿):此灯亮则表明冷干机正在运转工作。冷媒高低压故障指示灯(黄):此灯亮则表明冷干机内的高低压保护开关跳脱,需停机检查。电机过载故障指示灯(黄):此灯亮则表明压缩机工作电流过载,过载继电器已跳脱,需停机检查。

冷干机的启动过程: 1、接通电源,合上空气开关,此时设备仪表上的电源指示灯(红)亮。 2、若水冷式,应打开冷却水进出阀门; 3、按下绿色启动按钮,接触器吸合,待启动指示灯(绿)亮,5分钟后待 启动指示灯(绿)灭,  

压缩机开始运转,运行指示灯(绿)亮; 4、检查压缩机运转是否正常,有无异常响声,冷媒低压表指针是否下降至表上0.3~0.5MPa正

常范围内(R22制冷剂)。

5、如一切正常,再开启空气压缩机和空气进出口截止阀向冷干机送气,并且关闭空气旁路阀,

此时空气压力表会指示出空气出口压力;

6、观察5~10min后,经冷干机处理后的空气可达设计压力露点2~10℃,而此时冷媒高、低压

表指示正常范围如下:

冷媒低压:R22及R407C  0.3~0.5MPa        R134A   0.1~0.3Mpa

冷媒高压:R22及R407C  1.2~1.6MPa        R134A   0.7~1.1Mpa

7、慢慢打开自动排水器上的铜球阀,让空气中的冷凝水流入排水器中,经它排出设备外。

冷干机的停机过程:

1、打开旁通阀让压缩空气继续流入下游管道,然后关闭冷干机的出口阀门;

2、关闭冷干机的进口截止阀,并将冷干机卸压;

3、按红色停止按钮将冷干机关闭,并切断电源,打开手动排污阀放尽残余冷凝水。

冷于机操作时应注意的事项:1、应尽量避免冷干机长时间在无负荷状态下运转;2、禁止冷干机短时间连续开停,每次开机至少间隔10分钟,以免损坏制冷压缩机。

冷干机的保养要求对冷干机的保养是非常必要的,正确的使用和保养不仅可使冷干机达到使用要求,而且可延长其寿命。冷干机在出厂前都已测试,所有的控制功能也已校验,如果冷干机安装在洁净的环境里并在规定的环境温度范围内工作,冷干机将会长期地正常运转。常规的维护保养有以下几点:

一、设备运行时检查冷媒低压表读数是否在正常范围内。空气系统中,冷媒低压过低将会导致结霜或结冰,使压力损失增大并可能导致压缩机损坏。压力过高将使系统的制冷量减少。

二、自动排水器的保养:  应每天检查自动排水器排水情况,定期清洗排水器内滤网,以免堵塞而失去排水作用;

三、电动排水器的保养:

建议您每次检查压缩空气系统时,顺便按几下定时器上的手动测试按钮(TEST)检查电子排水器是否能正常得电排水。

在使用电子排水器的过程中,应特别注意以下几点:

1、定时器上TEST薄膜开关是手动测试按钮,每按动一次,排水器按照设定时间排放一次。此按钮在日常工作中用于随时检查排水情况。

2、电子排水器在使用中,可能会出现电磁阀关闭不严的情况,表现为一直漏气,通常该故障并非排水器本身质量所致,其原因是冷凝水太脏,其中的微小固体颗粒物进入阀芯与芯壳之间的间隙,将阀芯卡住。出现此故障时可用如下方法排除:

(1)反复多次按测试按钮直至故障排除(此方法对大多数的阀芯卡住极为有效)。

(2)如以上方法不能奏效,则需拆开电磁阀,清洗阀芯。

四、冷于机若另装有排污阀,须定时每日排污两次以上。五、风冷式的冷凝器,其翅片间距只有2~3mm极易被空气中的尘埃堵塞,造成散热不良,脏的冷

凝器将会使制冷系统冷凝压力升高,压缩机将会因过载而停止运行,所以应定期对它进行清洗,一般用压缩空气喷洗或用铜刷刷洗。亦可用加了清洗剂的低压水柱进行喷冲清洗,同理每年和根据需要清洗水冷凝器中的脏物及锈蚀等杂物。

六、水过滤器保养:  水过滤器主要为了防止冷却水中的固态杂质进入冷凝器而影响换热,所以应定期对滤网进行

    清洗,以免使水循环量不足,造成冷凝温度过高。

七、机组内部的保养:  在停机的时候,应定期对内部机件做吸尘清洗处理,并注意保护制冷系统, 以免损坏。八、随时注意设备前后左右是否保持通风良好,并要避免阳光直晒和一切热源。九、在满负荷情况下,检查通过冷干机气流的压力损失,如果比设计的值高 

(0.035Mpa),请反向清洗空气管路:将冷干机从系统中脱离出来,堵上所有排水管路,向空气系统中注入添加了清洗剂的水,保持4~6小时后用水泵使清洗剂从空气出口注入,空气进口排出,循环冲洗。最后用温水冲洗干净。如果压损仍然寸在,请与生产厂家联系。

风冷式冷干机的冷凝器翅片清洗方法:

机械式自动排水器清洗要点:将自动排水器分解,浸泡于肥皂水或洗洁精中再以毛刷刷洗。

电子排水器的清洗

(1)关闭过滤器,按测试(TEST)按钮,确保电子自动排水器与空压系统隔离(在零压力下);

(2)切断电子自动排水器电源;

(3)松开并取下连接线圈、控制器、接线头的长螺钉;

       

(4)松开线圈上防水螺帽取下线圈;

         

(5)用扳手松开铁芯外壳,取下动铁芯及弹簧;

         

(6)清洗电磁阀体、铁芯外壳、铁芯、弹簧;

       

(7)清洗好后按相反步骤重新装回即可。

冷干机的典型故障分析和处理  冷干机的故障主要来自电路系统和制冷系统两方面,故障的最终结果必然导致压缩机无法启动,制冷量下降或者设备损坏。正确判断各种故障产生的原因以及采取合理的排除方法,不但涉及电器和制冷技术方面的理论知识,更重要的是还须具备实践技能,有些故障可能是由几种原因造成的,首先必须对故障现象进行综合分析,才能找到有效的解决方法。另外,有些故障往往由于使用者不正确的使用和保养而引起,即所谓的“假性故障”,因此只有通过实际操作才能真正了解故障所在,找出正确的处理方法。现将冷干机的一些常见故障和排除方法重点说明一下:

故障现象原因分析解决方法
A.冷干机不工作

1.没有供电

2.保险丝熔断

3.线路断路或松动

1.检查供电系统

2.更换保险丝

3.根据电路图查线路

B.压缩机不运转

1.电源缺相或电压超出允许范围

2.接线不正确

3.继电器或接触器没有吸合

4.若压缩机为电容启动,启动电容损坏

5.高、低压保护开关不良

6.压缩机的机械故障,如卡缸

1.检查电源,使电源电压在额定范围内

2.根据电路图查线路

3.检查原因,更换或修理

4.更换启动电容

5.调整压力开关设定值,或更换压力保护开关

6.更换压缩机

C.冷媒高压过高引起冷媒压力故障灯亮

1.热负荷过大及进气温度太高

2.环境温度太高

3.冷凝器脏堵或冷却水量不足及冷却水温度过高

4.制冷系统中混入空气

5.风扇旋转方向不正确或风扇电机故障

6.膨胀阀异常

7.干燥过滤器堵塞

8.制冷剂灌充过多

1.降低热负荷和进气温度

2.改善通风条件,降低环境温度

3.清洗冷凝器或加大冷却水量及降低冷却水进水温度

4.查找原因,检修

5.将三条相线中的任意两条对换或更换风扇

6.更换膨胀阀

7.更换

8.放掉一部分冷媒(只有在上述原因都排除后才可进行此操作)

故障现象原因分析解决方法
D.冷媒低压过低引起冷媒压力故障灯亮

1.制冷剂不足或泄露

2.空气流量太小或负荷过轻

3.热气旁通阀未打开或不良

4.环境温度过低

1.检漏并重新抽真空添加制冷剂

2.增加压缩空气流量或负荷

3.调节热气旁通阀或更换

4.减少冷却水流量或关闭冷却水

E.压缩机运转电流过大引起热过载故障灯亮

1.热负荷过大及进气温度太高

2.环境温度过高

3.制冷剂不足,使其过热度太高

4.压缩过负荷

5.压缩机缺油或油位过低

6.压缩机轴承磨损或卡缸

1.降低热负荷和进气温度

2.改善通风条件,降低环境温度

3.添加制冷剂

4.减少压缩机启动次数

5.检查压缩机油位,补充润滑油

6.更换压缩机

F.蒸发器内部结冰,主要现象排水器不排水,打开排污阀有冰粒吹出

1.空气流量太小或负荷过轻

2.热气旁通阀未打开或不良,同时膨胀阀开启过大

3.蒸发器排水口堵塞,积水过多产生冰堵

1.增加压缩空气流量或负荷

2.调节热气旁通阀及膨胀阀或更换

3.疏通排水口,排净蒸发器冷凝水

G.设备运行正常但压降很大

1.进气压力低

2.管路阀门没有完全打开

3.管径过小、弯头太多或管路过长

4.蒸发器冰堵

5.空压机吸气过滤器堵塞

6.设备积水过多

7.设备所选型号处理能力太小

8.空气系统脏堵

1.增大进气压力

2.打开所有空气管路阀门

3.改善空气管路系统

4.参考F1-3

5.清洗或更换过滤器

6.检查排水系统,修理或更换

7.增加设备或更换更大处理量的设备型号

8.用清洗剂反向清洗

H.设备运行噪音过大

1.风扇叶片弯曲

2.风扇电机轴承磨损

3.制冷剂回液

4.压缩机损坏(卡缸、轴承磨损)

5.压缩机缺油

1.校正或更换

2.更换风机

3.检查膨胀阀,调节或更换

4.更换压缩机

5.检查油位水平,添加润滑油并检查油加热器是否工作正常

I.液管路结霜

1.高压侧阀门堵塞

2.干燥过滤器堵塞

1.打开阀门去除堵塞

2.更换

J.吸气管路结霜

1.膨胀阀异常

2.热气旁通阀未打开或不良

1.更换膨胀阀

2.调节热气旁通阀或更换

还有一些情况冷干机能正常运转但是效果不佳,这主要是由于工况变化,使制冷系统的工作状态发生了变化,引起制冷阀件失效,此时,就必须重新进行人工调节。

  冷干机配有可调节的热气旁通阀,它将根据负荷的变化自动调节回气压力,如此阀需调节,先拧开热气旁通阀顶部的螺帽,再用内六角旋转阀杆,顺时针旋转则加大开启度,逆时针旋转则减小开启度,调整时一次旋转1/4~1/2圈,运转3~5min左右,再观察制冷效果,若无变化或变化不显著,可再进行下一次调节,最后拧紧螺帽。为了冷干机的正常运行,请小心仔细地调节该阀门。

  我们知道,冷干机是由“四大件”和许多附件所组成的相互联系而又相互影响的复杂系统,因此,一旦出了故障,我们不应把注意力仅仅集中在某些局部上,而是要对整个系统进行全面检查,综合分析,只有这样,才能逐个消除疑点,最终找到产生故障的真正根源。另外,我们在对冷干机进行维修保养时,应注意保护制冷系统以免毛细管断裂,损伤引起冷媒泄漏。

 SLAD Series

Operation & Maintenance Instruction 

Purchase date
Type
Manufacture No.
  

CONTENT

一十、FTD  principle…………………………………………………………2

一十一、FTD Graphic components………………………………………………3

一十二、Attention to the installation  …………………………………4-6

一十三、SLAD series operation process …………………………………6-7

一十四、Conventional Instrument control panel specification ………7

一十五、FTD Start-up Process  ………………………………………………8

一十六、FTD  Shutdown process   ……………………………………………8

一十七、The maintenance requirement for FTD……………………………9-10

一十八、FTD Typical Fault Analysis  and Handling……………………11-14

  

FTD Technological process

FTD configuration process

FTD Main Graphic components

Attention to the installation

一、Standard Requirement for this FTD:No Ground bolt is needed but the foundation must   be horizontal and solid,which furthermore it should also concern the drainage system  height and drainage channel can be set.

二、The FTD is absolutely forbidden to be installed outside of a building or some sites with direct sunshine,rain ,high temperature ,bad ventilation, heavy dust,It needs to install the sites with temperatur between 0 0℃and 38 0℃. Wind-cooling FTD must be installed in room that With good ventilation equipment to maintain Wind-cooling FTD  for normal work. The Wind-cooling FTD that is installed in 空压房,must Takes the heat insulation measure between FTD and air Compressor。

  Wind-cooling type FTD will be placed on some sites that cooling air can through the condenser easily. The distance between the equipment and other machines should not less than one metre by way of conveniently operation and maintenance.

三、While assembling,some avoidance as follow:too long pipeline,too many  elbows,little pipe size in order  to lessen pressure drop.AT the inlet and outlet,bypass valves should be extraly equipped for checking and maintenance while in trouble.

四、Power connection wire may be Loose as a result of vibrates when install the FTD power, Please use the tool to screw tight,and pay attention to the following several points:

1、Rated voltage should be within士5%.

2、Electric cableline size must concern current value and line length.

3、The power for SLAD-0.5NF∽8.5NF must be specially supplied.

五、For The  Water-cooling type FTD ,The cooling or  cycling water must be intenerated. And its pressure must between 0.2Mpa and 0.4Mpa,its temperature not higher than 32℃. In order to prevent the Water-cooling type FTD from getting rusty or stopping up dirtily, Propose installing water filter in the cooling water of the Water-cooling type FTD.

六、At inlet of the FTD ,a pipeline filter is suggested to be equipped which may prevent solid impurities which size isnot not less than 3um and oil from polluting HECH copper tube surface.This case may affect heat-exchanging ability.

七、The FTD is suggested to be installed following the back cooler and gas tank on the process in order to debase Compressed-air inlet temperature of the FTD.Please carefully handle the FTD utilities and its working years.Assuming any problem and doubt,don’t hesitate to inquire us.

Installation and use of the electronic drainer

一、The filtration ball valve is both the isolation uses valve and the strainer, the contour is exquisite, and the clean is convenient; Rated pressure is 16Bar, condensed water entrance 1/2" , exports 1/2" Or 1/4" . Add it front of the electronic water drainer , guaranteed that the valve core is not easy to stop up (the following graphical representation).

二、At the time of the installation of electromagnetic valve, must pay attention to the flow direction of Condense water and the arrow point on the body of the valve, they should keep the same with direction; Valve body horizontal level install, up coil; The exit of the valve joins the tube (if hard PVC is in charge of) and leads to the sewer.

三、When connecting the timer,first back out the screw on the conncetion head,put the connection head out of the timer, take down outer cover (wiring cranium) join cable line  from outer cover line hole, the following picture shows wiring. After wiring is finished,put the wiring cranium back, Will insert the conncetion head to  the timer again. In order to prevent the moisture from entering the timer along the cable thread, tighten up the cable thread and the waterproof nuts of wiring cranium appropriate, tighten the fixed screw (M3 of cross)finally.The nut not only has the funtion of connection but also has the funtion of Sealed cushion,please make sure it must be tightened, Otherwise, The sealed cushion can not play waterproof function, will cause the troubles of coil and timer.

四、When establishes the timer, with the left side knob hypothesis time interval, with the right side knob hypothesis emissions time, the user should makes the adjustment according to the climate and the operating mode.

SLAD Series of Freezing Type Drier operation process

一、Examination before starting up

1. Check the refrigeration system: Observe High pressure gauge and Low pressure gauge on the control panel, two forms reach the equilibrium at certain pressure, and the pressure of this equilibrium is fluctuating up and down on the basis of level of the environment temperature, generally in (about 0.5MPa~ about 1.2MPa).

 

 2. Examin if the power voltage  is normal, (SLAD-0.5NF~SLAD-8.5NF equal AC220V/50HZ±5%;SLAD-10NF The above voltage is three phase AC380/220V/50HZ±5%).

3.Checking if  the pipeline is normal.The inlet air pressure should not be higher than working pressure at when selecting this type. And its temperature should not be higher than the set value while selecting this type.

4. The FTD that with the 30 cube Handling capacity or more has the compress engine oil heater, Must be heated (put through the power, the heater is heated automatically) for more than 8 hours before using in the apparatus for the first time, so as to ensure the temperature in the oil compressed engine is higher than ambient temperature by 10 ℃at least, otherwise, the compressor will be damaged seriously.

5.Supposing water cooling type is used,well then user should check if the cooling water can satisfy with the requirement. Its pressure is 0.15Mpa~0.4Mpa and temperature should be less than 32℃.

Conventional Instrument control panel specification 

Low pressure gauge on the refrigerant (Pressure dew point gauge),which will indicate saturated pressure value.High pressure gauge which will show condensation pressure value for the refrigerant.

Air pressure gauge which will indicate the compressed air pressure value at outlet of this FTD.

The change-over switch (black knob): Control and change on-sitely / long-range.

The indicator lamp of wait to start (green): After pressing down the start button, this lamp is bright, after 5 minutes later compressors start, falls darkly.Start botton(Green):Press this buttom,this FTD will be connected with  power and start running.

Stop button(Red).When press this button,this FTD will stop running.

Power indication light(Red):While it is light,it indicates the power has been connected with this equipment.

Operation indication light(Green):While it is light,it showes this FTD is running.High-low pressure protective on-off indication light for refrigerant.(Yellow):While it is light,it shows that protective on-off  has been released and this equipment should be stopped running and fixed.Indication light  while current overload(Yellow):When it is light,it indicates the compressor working current is overload,hereby overload relay has been released and this equipment should be stopped running and fixed.

Operation Procedure for this FTP:

1、Switch on the on-off,and power indication light will be red on the power control panel 2、If water cooling type is used,the inlet and outlet valves for cooling water should be open.

3、Press  the green  start button down, wait until the start indication light bright(Green), 5 minutes later, the start indication light off(Green),then the compressor begins to operate, the run  indication light bright(Green).

4、Check whether the operation of the compressor is in gear,i.e. whether some unnormal sound can be heard or whether the indication for low pressure gauge is drop to 0.3-0.5MPa normal range (R22 refrigerant).

5、Assuming everything is normal,open the compressor and the inlet and outlet valve , air will flow into FTD and meanwhile close the by-pass valve.At this moment air pressure indication gauge will show air outlet pressure.

6、Watch for 5~10minutes,the temperature of the air being treated by FTD can reach 2-10 ℃ of design pressure dew point, at this moment ,high pressure gauge and low pressure gauge point out the normal range is as follows :

Low pressure gauge: R22 and R407C  0.3~0.5MPa    R134A   0.1~0.3Mpa

High pressure gauge: R22 and R407C  1.2~1.6MPa   R134A   0.7~1.1Mpa

7、Open copper globe valve on the automatical drainer Slowly ,whereafter  the condensed water in the air will flow into the drainer and will be discharged.

Shut down Procedure for this FTP:

1、Open the by-pass valve and let the compressed air continue flowing into the downstream tube, then close the export valve of the FTD;

2、Air source should be closed first and FTD should be  relieved.

3、afterwards press the red STOP button to switch off FTD and cut off the power.Open the draining valve and then drain completely waste condensed water.

Pay attention to some proceeding while FTD is on operatin:1、Prevent FTD from running long time with no load as possible.2、Prohibit from starting and stopping FTD during a short time and Start the machine at intervals of 10 minutes at least each time for fear refrigerant compressor is damaged.

The maintenance requirement for Freezing Type Drier It is highly necessary to maintenance the FTD.Proper use and maintenance may guarantee the FTD to accomplish its usage but also last endurance time. The FTD has already tested, all control functions have been already check-up before dispatched from the manufacturer.  If the FTD is installed in the clean environment and works within the range of regulative ambient temperature, the FTD will run well  for a long time. Regular maintenance maintains the following several points:

一、Check the apparatus whether Low pressure gauge’s reading is in the normal range while operating. Among the air system, The refrigerant low pressure is too low will be able to cause the rime or to ice up, causes the pressure loss to increase and possibly to cause the compressor damage. Low pressure is too high will reduce systematic refrigeration.

二、The maintenance for automatical drainer: User should examin the water-draining condition and remove the garbage adhered to the filter meshwork to prevent the drainer from  being blocked and failing to drain.;

三、The maintenance for electronic drainer:

Advise you to check compressed air system,press test button several times(TEST) on the timer manually to check whethe rthe electronic drainer works  normally each time.

During the process of using the electronic drainer, should pay special attention to the following several points:

1、Test membrane switch on the timer is a manual test button, press once, drainer discharged once according to the setting  time. This button is used in checking the situation of draining off water at any time in routine duties.

2、In the use of electronic drainer may appear electromagnetic valve shut off loosely situation, shown as leaking gas all the time, usually this trouble is not due to drainer 's own quality,the reason is that  condense water is too dirty, there are  small solid particulate among the water, they enter the interval of core and  core shell ,block the core of the valve. We can be got rid of this trouble by the following method:

(3)Press the test button repeatedly  until the trouble clearing (this method is very effectively for most blocks).

(4)If the above method can't be effective, need to open the electromagnetic valve, wash the core of the valve.

四、Supposing extra drain valve is equipped,user should drain at least twice everyday at set time. 

五、Inside Wind-cooling condenser ,the spacing between two blades is only 2~3mm and easily         to be blocked by dust in air,which will baffle heat radiation. The dirty condenser will make the condensation pressure of the refrigeration system rise,and the compressor will stop running because of overload, so should wash it regularly, generally wash with the compressed air or coppery brush. Can also wash it  with the low-pressure  water added detergent. The same principle, wash incidentals such as dirt and corrosion in water condenser according to needs.

六、Maintenance for water-cooling type filter:Water filter will prevent solid imperity from entering condenser and guarantee nice heat exchange.User should clean filter meshwork termly in order not to make water badly cycle and high condensing temperature.

七、Maintenance for internal parts:During non-working period,user should clean or collect dust termly,and protect  the refrIgeration system from being demolished.

八、Good ventilation is necessary around this equipment at any moment and the FTD should be prevented from exposing in unshine or heat source.

九、In the full load situation, check the pressure lose of the air current through the FTD, if it is higher (0.035Mpa) than the value that is designed, please wash the air tube backward:Break the FTD away from the system, plug up all tubes that water flows through. pour water which added detergent into the air system, keep the situation for 4~6 hours,then pump the detergent into air export, and discharge it from air Import, circulation washes.  Finally rinse well with the warm water. If the pressure lose still exists here, please get in touch with the manufacturer.

Cleaning method for condenser Wing piece of wind-cooling FTD  condenser:

cleaning points for mechanical automatic drainer: Disassemble the drainer and dip it in  suds or cleaning agent,brush it by copper brush.

Cleaning for electronic automatic drainer

(8)Shut off the filter,press test (TEST) button, guarantee the electronic drainer isolates from air system (No pressure);

(9)Cut off the  power of the electronic automatic drainer.

(10)Takes down the connection coil, the controller, the long screw of the end of a thread;

       

(11)Remove the waterproof nut on the coil and takes down the coil;

         

(12)Open the outer covering of the ferrite core with the spanner pine, take down the ferrite core and the spring;

         

(13)Wash the body of the electromagnetic valve, core outer cover, core, spring;

       

(14)Install again according to the step on the contrary after washing well.

Typical trouble analysis and settlement for FTD   The freezing dryer troubles mainly exist in electric circuits and refrigeration system. The results of these troubles are system is shut down, reduction of refrigerating capacity or equipment damage. To locate the trouble spot correctly and take practical measures concern with theories of refrigerant and electrical techniques, some thing more important is experiences in practice. Some troubles may caused by several reasons first of all analyze the refrigerant equipment synthetically to find out the solution. In addition some trouble is caused by improper use or maintenance, this is called “false” trouble, so the right way to find the trouble is practice. The common troubles and disposing measures are as follows:

Trouble phenomenonCause AnalysisDisposal
A.The FTD can not work

1. No power supply

2. circuit fuse melted 

3. Wire disconnected or loosed

1. Check power supply

2. replace the fuse

3. Check the circuit according to the circuit diagram

B.The compressor can’t work

1. Fewer phase in power supply, improper voltage

2. Wiring is incorrect

3. Bad contacts and Relay, the power is not put through

4. Supposing the compressor is started by capacitor,probably the  capacitor has be damaged.

5.High & low pressure(or voltage) protective switch problem

6.Mechanical trouble of compressor,such asjammed ylinder

1. Check power supply, control power supply in proper voltage 

2. Check the circuit according to the circuit diagram

3.Inspection reasons, replacement or repair

4. Replace starting capacitor

5. Regulate voltage switch set value, or replace damaged switch

6. Replace compressor

C.The efrigerant high pressure is too high cause fault light1. Heat load oversized and inlet air temperature is too high

2. Ambient temperature is too high

3. The condenser dirty stops up or Cooling water shortage and Cooling water temperature is too high

4. Gases get in the refrigerating system 

5. Fan rotation direction incorrect or fan motor fault

6. Expansion valve abnormality

7. Dry filter plug

8. Overfilling of refrigerant

1. Reduce heat load and Lower the inlet temperature

2. Improve ventilation condition and Lower Ambient temperature

3. Clean pipes of condenser or increase cool water cycling amount or Lower r inlet temperature of Cooling wate

4. Find out the reason, overhaul

5. Arbitrary two exchange in line of Phase three  or changing fan

6. Replaces the expansion valve

7. Replaces

8. Discharge surplus refrigerant(may carry on this operation Only after the above reasons are all excluded)

Trouble phenomenonCause AnalysisDisposal
D.The refrigerant low pressure is too low cause fault light

1. Insufficient refrigerant or leaking

2. Air flow is too small or Too small load

3. Steam bypass valve is not open or bad

4. Ambient temperature is too low

1. find leaking sports, repair and vacuumize once more, refill refrigerant

2. Increase air flow and heat load

3. Regulate hot air bypass valve or replace

4. Reduced cooling discharge of water or Closed cooling water

E.The operation currentis overload, cause Causes hot overload lamp bright

1. over heavy air load, bad ventilation

2. Too high ambient temperature 3. Insufficient refrigerant cause high temperature

4. Over load for the compressor 5. The compressor is out of gas or the oil level is excessively low

6. Compressor bearing attrition or Stuck cylinder

1. Lower the heat load and inlet air temperature

2. Improve ventilation condition and lower Ambient temperature 

3. Add Refrigerants

4. Reduce start & stop times 

5. Inspection compressor oil level,Supplements the lubricating oil

6. Replaces the compressor

F. Water in evaporator has frozen, this manifestation is that no action of the drainer.Consequently when the waste valve is opened, there are ice particles blown out.1. Little air flow, low load

2. The heat air bypass valve is not open or bad,Simultaneously expansion valve opening is oversized

3. The inlet of the evaporator has veen jammed and too much water-collection,Produces the ice barrier

1. Increase compressed-air flow quantity or load

2. Adjust heat air bypass  valve and expansion valve or replaces

3. Dredge the drainer  and completely drain the waste water in the condenser

G.The Freezing Type Dryer may normaly run whereas Too much pressure drop

1. Air admission Pressure is low

2. The pipeline valves haven’t been totally open

3. Little size pipeline,and too many elbows or too long pipeline 

4.The evaporat has been frozen

5. Air compressor Inhale filter is plug 

6. There is too much water accumulation of the equipment

7.The handling capacity of the selected equipment is too small

8. Air system dirty and Plugging

1. Increase air admission Pressure 

2. Open all valves which air must flow by

3. Meliorate air flow system

4. Reference F1-3

5. Clean or replace the filter 

6. Check the drainage system, repair or change

7. Increase the equipments or change the equipment type of bigger handling capacity

8. Cleans with the detergent  reversion

H.The noice of the  equipment is oversized

1. Blade of the fan is crooked

2. Fan motor bearing wear and tear

3. refrigerant return

4. Compressor damage (Stuck cylinder or bearing attrition )

5. Compressor lacks oil

1.Adjustment or replacement

2. Replaces the air blower

3. Inspects the expansion valve,  adjustment or replacement

4. Replaces the compressor

5. Inspection oil level,Supplements the lubricating oil and Check whether the oil heater works normally

I.The tube of liquid Frosting

1. The high-pressure side valve plug

2. Dry filter plug

1. Open the valve to remove pulg

2. replace

J.Suction tube  frosting

1. Expansion valve abnormality

2. Hot air bypass valve is not open or bad

1. Replaces the expansion valve

2. Regulate hot air bypass valve or replace

Also has some situations,the FTD works  normaliy but Low efficiency,it is mainly because the changed case caused the refrigerating system condition transformed and refrigeration Valve failure. Here it is necessary to adjust it manually.

FTD is furnished with the adjustable hot air by-pass valve, it will adjust Back pressure automatically according to the change of load. If the valve must to be adjust,first turn on the cap nut in the top of hot air by-pass valve,then  revolves the valve lever with spanner, Clockwise rotation enlarges opens, counterclockwise rotation reduces opens, the  turnning range shall be 1/4—1/2 circle at one time.whereafter operate this equipment for 3—5 minutes,check the performance and by it to decide if readjustment is needed anymore, finally screws tight the cap nut.

As we know that the FTD is complex system which  consists of four big units and many accessories,that are interactively  effective to each other. Hereby in case trouble occurs, we shall not only pay attention to one part but also take overall inspection and analysis to eliminate suspicious parts step by step and finally find out the cause. In addition when repair or maintenance works performed  for the FTD, user shall pay attention to preventing refrigeration system from being damaged  , especially the damages to capillary tubes. Otherwise refrigerant leaking may engendered.