最新文章专题视频专题问答1问答10问答100问答1000问答2000关键字专题1关键字专题50关键字专题500关键字专题1500TAG最新视频文章推荐1 推荐3 推荐5 推荐7 推荐9 推荐11 推荐13 推荐15 推荐17 推荐19 推荐21 推荐23 推荐25 推荐27 推荐29 推荐31 推荐33 推荐35 推荐37视频文章20视频文章30视频文章40视频文章50视频文章60 视频文章70视频文章80视频文章90视频文章100视频文章120视频文章140 视频2关键字专题关键字专题tag2tag3文章专题文章专题2文章索引1文章索引2文章索引3文章索引4文章索引5123456789101112131415文章专题3
当前位置: 首页 - 正文

液位变送器说明书翻译

来源:动视网 责编:小OO 时间:2025-09-30 08:27:03
文档

液位变送器说明书翻译

InstructionsforLP80411/00+TKE4202/24liquidleveltransmitterThecorepressuresensitivedeviceinLP80411/00+TKE4202/24seriespressuretransmitteruseshigh-qualitysiliconpiezoresistivecoresfilledwithoil.Thetransmittercanconvertmillivoltsignalsfromtransduce
推荐度:
导读InstructionsforLP80411/00+TKE4202/24liquidleveltransmitterThecorepressuresensitivedeviceinLP80411/00+TKE4202/24seriespressuretransmitteruseshigh-qualitysiliconpiezoresistivecoresfilledwithoil.Thetransmittercanconvertmillivoltsignalsfromtransduce
Instructions for LP80411/00+TKE4202/24 liquid level transmitter

The core pressure sensitive device in LP80411/00+TKE4202/24 series pressure transmitter uses high-quality silicon piezoresistive cores filled with oil. The transmitter can convert millivolt signals from transducers to standard distant transmission current signals, which can be easily connected to interface cards of PC, control instruments, intelligent instruments and PLC. This product can be widely used in industrial process control, petroleum, chemical, and metallurgy industries.

This product is accord with GB 3836.1-2000 “Electrical apparatus for explosive gas atmospheres—Part 1: General requirements” and GB 3836.4-2000 “Electrical apparatus for explosive gas atmospheres—Part 4: Intrinsic safety ‘i’ ”. IP rating of the instrument is Exia II CT4.

1. Specification

      (1) Operating temperature: 0~100℃

      (2) Standard accuracy

      (3) Measurement resolution:

         Grade 0.1, ±0.1;

         Grade 0.3, ±0.3;

         Grade 0.5, ±0.5

         Standard accuracy is expressed in percentage of measurement range

      (4) Thermal zero shift

        If atmosphere temperature was shift from operating temperature, thermal zero shift is not great than 0.03%FS/℃.

(5) Thermal sensitivity shift

If atmosphere temperature was shift from operating temperature, full range shift is not great than 0.03%FS/℃.

(6) Insulation resistance

Under standard operating condition, insulation resistances between terminals of transmitter and ground can not below 20MΩ/250V.

(7) Explosion proof performance

Exia II CT4

(8) 4~20mA hermaphroditic connector

(9) Multi-level electric protection

2. Configuration   

Figure 1 is the transmitter configuration sketch. LP80411/00+TKE4202/24liquid level transmitter is consist of shell, amplifier, terminal blocks and hollow wire. Point meter and LCD display can be concluded according to custom’s requirement.

3. Installation

      (1) Install the device in a place where can easily operate and maintenance it.

      (2) Do not install near a vibration source.

      (3) Do not install near a thermal source.

      (4) Metal transducer should settle down on the vessel floor.

4. Electrical connections

      Open the back cover of the device, there are connection terminals. The below figure is a sketch of the power connection.

      Connection diagram of the intrinsically safe system shows in the below figure.

Parameters in the intrinsically safe system show meet the below regulations:

Uo≤Ui;  Io≤Ii;  Po≤Pi;  Cc≤Co-Ci;  Lc≤Lo-Li.

5. Zero point and gain adjustment

Pressure gauge has been calibrated before shipment. No other adjustment should take. If zero point and full range shift occurred during operation, calibration should be taken on the  pressu re sou rce  with high order accuracy every year. Here is how adjustment takes:

Adjust Potentiometer Z to zero with no pressure input, to make output current reach 4.000mA. Adjust gain of Potentiometer S to make output current reach 20.000mA with full range pressure. Repeat these operations to make the zero point and full range of the pressure gauge reach standard values.

6. Safety operation notice

(1) Avoid impact on the circuit performance during shipment and installation.

(2) Never intentionally touch isolating membrane in entry of the transmitter.

(3) Electric connection should strictly accord with the sketches to avoid damage amplifier circuit.

(4) During the installation of the input liquid transmitter, conducting wire can only be used for deliver the products.

(5) Transducer should be regularly cleaned.

(6) The water-proof wire should be protected to avoid abrasion, puncture and scratch. If those problems occur, maintenance fees would be charged by the company.

(7) Please feel free to contact us during the service. If abnormal problems occurred, do not open the device for maintenance without the guidance of us.